N300

Features

Powerful high torque using advanced sensorless vector control Powerful operation with advanced sensorless vector control

100% continuous torque operation within a 1:10 speed range on general-purpose motors

Powerful operation is possible for two motors at the same time.

Drastic reduction of rotational fluctuation at low speed On-line , Off-line auto-tuning Various communication protocol

Fan on, off selection

PID operation Deceleration and stop at power failure P/ PI control selection

Selection and application of necessary functions only

Conformity to Global Standards

Specifications

200V Class

Item (N300) 055
LF
075
LF
110
LF
150
LF
185
LF
220
LF
300
LF
370
LF
450
LF
550
LF
Applicable Motor(kw) 5.5 7.5 11 15 18.5 22 30 37 45 55
Rated Output Current(A) 24 32 46 64 76 95 121 145 182 220
Rated Input Voltage(kVA) 8.3 11 15.9 22.1 26.3 32.9 41.9 50.2 63 76.2
Braking Dynamic Braking Built-in BRD circuit External dynamic braking unit(option)
Minimum Value of Resistor(Ω) 17 17 17 - - - - - - -
Rated Output Current(A) 3-phase 200~240V(±10%) 50Hz/60Hz
Rated Output Voltage(V) 3-phase 200~240V(According to supply voltage)
Control Method Line to line sine wave PWM
Output Frequency Range 0.1~400Hz
Frequency Accuracy Digital ±0.01% of maximum frequency, analog ±0.2%(25℃±10℃)
Frequency Resolution Digital setting "0.01Hz, analog setting "Maximum frequency/4000(O terminal:12bit/0~+10V, 02 terminal :12bit/-10~+10V)
V/F Characteristics V/F free setting(30-400Hz of base frequency), Constant torque and reduced torque of V/F control, sensorless vector control
Speed Fluctuation ±0.5%(Sensorless vector control)
Overload Capacity 150%/60sec, 200%/0.5sec
Starting Torque 200%,0.5Hz(Sensorless vector control), 150% at around 0Hz(Sensorless vector control with a motor one size frame down)

 

DC Braking Performs at start, under set frequency at deceleration, via an external input(braking force, time and operating frequency)
Input Signals Fre
quency Setting
Operator Set by up(▲)key down(▼)key
External Signal DC 0~+10V, -10~+10V(Input impedance 10Kohm), 4~20mA(Input impedance 100ohm)
External Port Set by RS 485
Forward/
Reverse Start/Stop
Operator Run / Stop key(Change FW/RV by function command)
External Signal RW Run /Stop(NO contact), RV set by terminal assignment(NO/NC selection), 3-wire input possible
External Port Set by RS 485
Intelligent Input Terminals Selection of 8 function from RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run-stop), EXT(External trip), USP(Unattended start protection), CS(Change to/from commercial power supply), SFT(software lock), AT(analog input selection), SET3(Third motor constants setting), RS(Reset), STA(3-wire start), STP(s-wire stop), F/R(3-wire fwd./rev.), PID(PID on/off), PID(PID reset), CAS(Control gain setting), UP/DWN(Remote-controlled accel./decel), UDC(Remote-controlled data clearing), OPE(Operator control), SF1-SF7(Multispeed bit command 1-7), OLR(Overload limit change), TL(Torque limit change), TRQ1, TRQ2(Torque limit selection(1),(2)) PPI(P/PI selection), BOK(Brake verification), ORT(Orientation), LA(LAD cancel), PCLR(Positioning deviation reset), STAT(90-degree phase difference permission), NO(NOT selected)
Thermistor Input One terminal(PTC characteristics)
Output Signals Intelligent Monitor Output Terminals Analog voltage, Analog current, Pulse line output
Intelligent Output Terminals Five open collector terminals and one NO-NC combined contact. Selection from : Run(Run signal), FA1(Frequency arrival signal(at the set frequency)), FA2(Frequency arrival signal(at or above the set frequency)). OL(Overload advance notice signal), OD(Output deviation for PID control), AL(Alarm signal), FA3(Frequency arrival signal(only at the set frequency)), OTQ(Over-torque), IP(Instantaneous power failure signal), UV(Under-voltage signal), TRQ(In torque limit), RNT(Operation time over), ONT(Plug in time over), THM(Thermal alarm), BRK(Brake release), BER(Brake error), ZS(Zero speed), Frequency arrival signal (at or above the set frequency(2)), Frequency arrival signal(Only at the set frequency(2)), OL2(Overload advance notice signal(2)), (Terminal 11-13 or 11-14 are automatically configured as AC0-AC2 or AC0 - AC3 when alarm code output is selected at C62.)
Display Monitor Output frequency, Output current, motor torque, Scaled value of output frequency, Trip history, I/O terminal condition, Input power, Output voltage
Other Functions V/F free-setting(up to 5 points), Frequency upper/lower limit, Frequency jump, Accel./decel. curve selection, Manual torque boost value and frequency adjustment, Analog meter tuning start frequency setting, Carrier frequency setting, Electronic thermal free-setting, External frequency output zero/span reference, External frequency input via start/end, analog input selection, Retry after trip, Restart after instantaneous power failure, Various signal outputs, Reduced voltage start, Overload restriction, Default value setting, Deceleration and stop after power failure, AVR function, Fuzzy accel./decel., Auto-tuning(on-line/off line), High-torque multioperation
Carrier Frequency Range 0.5~15kHz
Protective Functions Over current protection, Overload protection, Braking resistor overload protection, Over-voltage protection, EEPROM error

Environmental
Conditions

Ambient
Operating/
Storage
Temperature
-10℃~50℃/ -20℃~60℃
Vibration 5.9㎨(0.6G), 10~55Hz 2.94㎨(0.3G), 10~55Hz
Location Less than 1,000m of altitude, indoors(no corrosive gas nor dust)
Color Grey/Munsell No 8.5 YR 6.2/0.2
Option Feedback
Option
Vector control with sensor
Digital Input
Option
4 Column, BCD, 16bit binary
Other Option EMI filters, Input/output reactors, DC reactors, Radio noise filters, Braking unit, Braking resistor, LCR filter

400V Class

Item(N300)
055
HF
075
HF
110
HF
150
HF
185
HF
220
HF
300
HF
370
HF
450
HF
550
HF
750
HF
900
HF
1100
HF

1320
HF

Applicable
Motor(kW)
5.5
7.5 11 15 18.5 22 30 37 45 55 75 90 110 132
Rated Output Current(A)
12
16 23 32 38 48 58 75 90 110 149 176 217 260
Rated Input Voltage(kVA)
8.3
11 15.9 22.1 26.3 33.2 40.1 51.9 62.3 76.2 103.2 121.9 150.3 180.1
Braking Dynamic
Braking
Built-in
BRD circuit
External Dynamic Braking Unit(Option)
Minimum
Value
of
Resistor
(Ω)
0.85 0.6 0.4 - - - - - - - - - - -
Rated Output Current(A) 3-phase 380~480V(±10%) 50Hz/60Hz
Rated Output Voltage(V) 3-phase 380~480V(±10%) 50Hz/60Hz
(According to supply voltage)
Control Method Line to line sine wave PWM
Output
Frequency
Range
0.1~400Hz
Frequency
Accuracy
Digital ±0.01% of maximum frequency, Analog ±0.2%(25℃±10℃)
Frequency Resolution Digital setting "0.01Hz, Analog setting "Maximum frequency/4000(O terminal:12bit/0~+10V, 02 terminal :12bit/-10~+10V)
V/F
Characteristics
V/F free setting(30-400Hz of base frequency), Constant torque and reduced torque of V/F control, sensorless vector control
Speed
Fluctuation
±0.5%(Sensorless vector control)
Overload
Capacity
150%/60sec, 200%/0.5sec
Starting Torque 180%,0.5Hz
DC Braking Performs at start, under set frequency at deceleration, via an external input(braking force, time and operating frequency)
Input
Signals
Frequency
Setting
Oper
ator
Set by up(▲)key down(▼)key
Exter
nal Signal
DC 0~+10V, -10~+10V(Input impedance 10Kohm), 4~20mA(Input impedance 100ohm)
Exter
nal
Port
RS 485
Forward/
Reverse
Start/
stop
Oper
ator
Run / Stop key(Change FW/RV by function command)
Exter
nal Signal
RW RUN/STOP(NO contact), RV set by terminal assignment(NO/NC selection), 3-wire input possible
Exter
nal
Port
Set by RS 485
Intelligent Input Terminals Selection of 8 function from RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run-stop), EXT(External trip), USP(Unattended start protection), CS(Change to/from commercial power supply), SFT(Software lock), AT(Analog input selection), SET3(Third motor constants setting), RS(Reset), STA(3-wire start), STP(S-wire stop), F/R(3-wire fwd./rev.), PID(PID on/off), PID(PIDreset), CAS(Control gain setting), UP/DWN(Remote-controlled accel./decel), UDC(Remote-controlled data clearing), OPE(Operator control), SF1-SF7(Multispeed bit command 1-7), OLR(Overload limit change), TL(Torque limit change), TRQ1, TRQ2(Torque limit selection(1),(2)) PPI(P/PI selection), BOK(Brake verification), ORT(Orientation), LA(LAD cancel), PCLR(Positioning deviation reset), STAT(90-degree phase difference permission), NO(NOT selected)
Thermistor
Input
One terminal(PTC characteristics)      
Output
Signals
Intelligent
Monitor
Output
Terminals
Analog voltage, Analog current, Pulse line output    
Intelligent
Output
Terminals
Five open collector terminals and one NO-NC combined contact. Selection from : Run(Run signal), FA1(Frequency arrival signal(at the set frequency)), FA2(Frequency arrival signal(at or above the set frequency)). OL(Overload advance notice signal), OD(Output deviation for PID control), AL(Alarm signal), FA3(Frequency arrival signal(only at the set frequency)), OTQ(Over-torque), IP(Instantaneous power failure signal), UV(Under-voltage signal), TRQ(In torque limit), RNT(Operation time over), ONT(Plug in time over), THM(Thermal alarm), BRK(Brake release), BER(Brake error), ZS(Zero speed), Frequency arrival signal (at or above the set frequency(2)), Frequency arrival signal(Only at the set frequency(2)), OL2(Overload advance notice signal(2)), (Terminal 11-13 or 11-14 are automatically configured as AC0-AC2 or AC0 - AC3 when alarm code output is selected at C62.)
Display Monitor Output frequency, Output current, Motor torque, Scaled value of output frequency, Trip history, I/O terminal condition, Input power, Output voltage   
Other Functions V/F free-setting(up to 5 points), Frequency upper/lower limit, Frequency jump, Accel./decel curve selection, Manual torque boost value and frequency adjustment, Analog meter tuning start frequency setting, Carrier frequency setting, Electronic thermal free-setting, External frequency output zero/span reference, External frequency input via start/end, analog input selection, Retry after trip, Restart after instantaneous power failure, Various signal outputs, Reduced voltage start, Overload restriction, Default value setting, Deceleration and stop after power failure, AVR function, Fuzzy accel./decel., Auto-tuning(on-line/off line), High-torque multioperation
Carrier
Frequency
Range
0.5~15kHz
Protective
Functions
Over current protection, Overload protection, Braking resistor overload protection, Over-voltage protection, EEPROM error
Environmental
Cconditions
Ambient
Operating/
Storage
Temperature
-10℃~50℃/ -20℃~60℃
Vibration 2.94㎨(0.3G), 10~55Hz
Location Less than 1,000m of altitude, indoors(no corrosive gas nor dust)
Color Grey/Munsell No 8.5 YR 6.2/0.2
Option Feedback
Option
Vector control with sensor
Digital
Input
Option
4 COLUMN BCD, 16bit binary
Other Option EMI filters, Input/output reactors, DC reactors, Radio noise filters, Braking unit, Braking resistor, LCR filter